The programmer for addressable devices PKU-1
|
 |
 |
 |
|
 |
The programmer for addressable devices PKU-1 is a small portable device with a battery 9V.
PKU-1 is used to set, check and adjust parameters of addressable devices. The list of these devices is given in the Table No.
The programmer PKU-1 provides:
- checking and changing the following parameters: address, configuration, activation delay, holdup, address number, the date of the last service, activation threshold ∆Ò/t;
- only parameters’ checking: dust level, serial number, software version;
- correction of dust level after the cleaning of the smoke chamber.
|  |
 |
  |
The appearance of the PKU-1 is given in the picture No.1
To connect the addressable detectors a special socket is used which is on the programmer’s underside (picture No.2)
|
| Picture No.1 Picture No.2 | |
Picture No.3
|
To connect the other devices you have to use a special adapter (picture No.3). The plug is inserted into the socket of PKU-1 and the wires are connected to the device which you want to program.
To turn the programmer on push any button and hold it for 2 seconds. The programmer will turn off if you do not connect a device within 20 seconds.
After you connect a device to the programmer the parameters of this device appear on the screen.
If you do not push any button within 60 seconds the programmer will turn off.
|
| Currency | 7,5 – 9 V |
| Dimensions | 95x150x65 mm |
| Weight | 350 g |
| Working temperature | +5 - +55 °C |
| Device | Description | Parameters |
| 212/101-64-À2R1 | Addressable combined optoelectronic smoke differential-peak heat detector | Address
Dust level
Serial number
Indication
Date of the last service
Software version
Activation threshold ∆Ò/t
|
| AFD-H 29A2R | Addressable differential-peak heat detector | Address
Serial number
Software version
Activation threshold ∆Ò/t
|
| AFD-S 64 | Addressable optoelectronic smoke detector | Address
Dust level
Serial number
Indication
Date of the last service
Software version
|
| IPR 513-11 | Addressable manual call point | Address
Serial number
Software version
|
| AM-1 | Address assignment point | Address
Serial number
Configuration
Software version
|
RM-1
RM-2 | Relay module | Address
Serial number
Configuration
Activation delay
Holdup
Address number
Software version
|
|
|